PRODUCTS

IEC Single Core 8.7/15(17.5)KV XLPE Insulated
Description

Application:
       This cable is used for urban networks. It can be installed aerially, in conduit, on open trays and in underground ducts 
Operating temperature:
       90 & & &,,,,,
 
Voltage rating:
       8.7/10,8.78/15(17.5)KV
Construction:
      Conductor: Compact round stranded copper or aluminium
      Conductor Shield: Semi-conducting tape and /or semi-conducting cross-linked polyethylene
      Insulation: Cross-linked polyethylene
      Insulation Shield: Semi-conducting cross-linked polyethylene
      Shield: Copper tape shield
       Filler: Polypropylene (Nonhygroscopic material)
       Binding Tape: Polyester and/or non-woven tape (Optional: water blocking tape)
       Bedding: Black polyethylene (Optional: polyvinyl chloride)
       Armour: Aluminium wire armoured
      Sheath: Black polyvinylene (ST7) (Optional: polyvinyl chloride)

Insulation colour:
     Natural

Followed standard:
      IEC60502-2,IEC60228
Construction data: 

Nominal Cross sectional area Reference conductor diameter Nominal insulation thickness Approx overall diameter Approx weight of cable Approx overall diameter Approx weight of cable
Unarmoured Aluminum wire armoured
AL CU AL CU
mm2 mm mm mm kg/km kg/km mm kg/km kg/km
25 6.0 4.5 22.0 505 665 33.0 2630 2785
35 7.1 4.5 23.0 565 795 34.0 2770 3050
50 8.4 4.5 24.0 635 930 35.0 2965 3260
70 10.0 4.5 26.0 740 1175 37.0 3215 3650
95 11.7 4.5 27.0 870 1490 39.0 3495 4115
120 13.2 4.5 30.0 1050 1855 41.0 3865 4675
150 14.5 4.5 31.0 1175 2150 43.0 4125 5105
185 16.2 4.5 33.0 1325 2495 45.0 4415 5585
240 18.4 4.5 35.0 1550 3075 47.0 4845 6375
300 20.6 4.5 38.0 1835 3815 49.0 5335 7320
400 23.8 4.5 41.0 2185 4670 53.0 6010 8490
500 26.6 4.5 45.0 2525 5615 58.0 7275 10360
630 30.0 4.5 49.0 3005 6895 62.0 8160 12055
800 34.0 4.5 54.0 3835 8518 67.0 9370 14050
1000 38.2 4.5 61.0 4655 10850 72.0 10625 16815
 