PRODUCTS

IEC Single Core 12/20(24)KV XLPE Insulated
Description

Application:
       This cable is used for urban networks. It can be installed aerially, in conduit, on open trays and in underground ducts 
Operating temperature:
       90 & & &,,,,,
 
Voltage rating:
     12/20(24)KV
Construction:
      Conductor: Compact round stranded copper or aluminium
      Conductor Shield: Semi-conducting tape and /or semi-conducting cross-linked polyethylene
      Insulation: Cross-linked polyethylene
      Insulation Shield: Semi-conducting cross-linked polyethylene
      Shield: Copper tape shield
       Filler: Polypropylene (Nonhygroscopic material)
       Binding Tape: Polyester and/or non-woven tape (Optional: water blocking tape)
       Bedding: Black polyethylene (Optional: polyvinyl chloride)
       Armour: Aluminium wire armoured
      Sheath: Black polyvinylene (ST7) (Optional: polyvinyl chloride)

Insulation colour:
     Natural

Followed standard:
      IEC60502-2,IEC60228
Construction data: 

Nominal Cross sectional area Reference conductor diameter Nominal insulation thickness Approx overall diameter Approx weight of cable Approx overall diameter Approx weight of cable
Unarmoured Aluminum wire armoured
AL CU AL CU
mm2 mm mm mm kg/km kg/km mm kg/km kg/km
35 7.1 5.5 25.0 650 880 36.0 3085 3310
50 8.4 5.5 26.0 735 1030 38.0 3100 3405
70 10.0 5.5 28.0 850 1280 39.0 3540 3975
95 11.7 5.5 30.0 995 1615 41.0 3830 4445
120 13.2 5.5 32.0 1145 1955 43.0 4130 4940
150 14.5 5.5 34.0 1290 2265 45.0 4415 5395
185 16.2 5.5 35.0 1430 2600 47.0 4740 5910
240 18.4 5.5 38.0 1675 3205 49.0 5380 6905
300 20.6 5.5 40.0 1970 3615 51.0 5650 7290
400 23.8 5.5 44.0 2335 4815 55.0 6305 7585
500 26.6 5.5 47.0 2785 5865 59.0 7075 10160
630 30.0 5.5 51.0 3285 7180 63.0 7930 11820
800 34.0 5.5 56.0 4025 8705 68.0 9135 13810
1000 38.2 5.5 63.0 4865 11055 75.0 10560 16755
 
,,DDD