PRODUCTS

AS/NZS Single Core 12.7/22KV XLPE Insulated
Description

Application:
       This cable is used for urban networks. It can be installed aerially, in conduit, on open trays and in underground ducts 
Operating temperature:
       90 & & &,,,,,
 
Voltage rating:
       12.7/22KV
Construction:
      Conductor: Compact round stranded copper or aluminium
      Conductor Shield: Semi-conducting tape and /or semi-conducting cross-linked polyethylene
      Insulation: Cross-linked polyethylene
      Insulation Shield: Semi-conducting cross-linked polyethylene
      Shield: Copper wire shield
       Filler: Polypropylene (Nonhygroscopic material)
       Binding Tape: Polyester and/or non-woven tape (Optional: water blocking tape)
      Sheath: Black polyvinylene (Optional: polyvinyl chloride)

Insulation colour:
     Natural

Followed standard:
      AS/NZS1429.1,AS/NZS1125
Construction data: 
      
Copper conductor,10KA Fault Level   

 
Nominal Cross sectional area Reference conductor diameter Nominal insulation thickness Nominal diameter over insulation Nominal screen area on each core Number and nominal diameter of screen wires Nominal over screen wire Approx overall diameter Approx weight of cable Max.
puling tension
Min.bending radius
During pulling Set in position
mm2 mm mm mm mm2 mm mm mm kg/km KN mm mm
35 7.1 5.5 19.1 34.4 24/1.35 23.5 27.5 1150 2.5 500 330
50 8.4 5.5 20.3 48.7 34/1.35 24.8 28.7 1400 3.5 520 340
70 10.0 5.5 22.0 68.7 48/1.35 26.5 30.5 1850 4.9 550 370
95 11.7 5.5 24.0 68.7 48/1.35 28.3 32.5 2155 6.7 580 390
120 13.2 5.5 25.5 68.7 48/1.35 30.0 34.5 2450 8.4 610 410
150 14.5 5.5 27.0 68.7 48/1.35 31.5 35.5 2750 11.0 640 430
185 16.2 5.5 28.5 68.7 48/1.35 33.0 37.5 3105 13.0 670 450
240 18.4 5.5 31.0 68.7 48/1.35 35.5 40.0 3755 17.0 720 480
300 20.6 5.5 33.2 68.7 48/1.35 38.0 43.0 4400 21.0 770 510
400 23.8 5.5 36.5 68.7 48/1.35 41.0 46.5 5350 28.0 830 550
500 26.5 5.5 39.0 68.7 48/1.35 43.5 49.0 6400 35.0 880 590
630 30.0 5.5 43.0 68.7 48/1.35 47.5 53.5 7650 44.0 960 640
800 36.0 5.5 49.0 68.7 48/1.35 53.5 60.0 9650 56.0 1070 720
1000 40.2 5.5 54.5 68.7 48/1.35 59.0 65.5 11600 70.0 1180 780




 























       Aluminum conductor,10KA Fault Level 
Nominal Cross sectional area Reference conductor diameter Nominal insulation thickness Nominal diameter over insulation Nominal screen area on each core Number and nominal diameter of screen wires Nominal over screen wire Approx overall diameter Approx weight of cable Max.
puling tension
Min.bending radius
During pulling Set in position
mm2 mm mm mm mm2 mm mm mm kg/km KN mm mm
35 7.1 5.5 19.5 22.7 40/0.85 22.5 27.0 810 1.8 480 320
50 8.4 5.5 20.5 32.9 23/1.35 25.0 29.0 980 2.5 520 340
70 10.0 5.5 22.0 45.8 32/1.35 26.5 30.5 1200 3.5 550 370
95 11.7 5.5 23.8 61.5 43/1.35 28.0 32.5 1500 4.8 580 390
120 13.2 5.5 25.0 68.7 48/1.35 29.5 34.0 1700 6.0 610 410
150 14.5 5.5 26.5 68.7 48/1.35 31.0 35.5 1800 7.5 630 420
185 16.2 5.5 28.0 68.7 48/1.35 32.5 37.0 1950 9.3 670 440
240 18.4 5.5 30.5 68.7 48/1.35 35.0 39.5 2200 12.0 710 470
300 20.6 5.5 32.8 68.7 48/1.35 37.5 42.5 2450 15.0 760 500
400 23.8 5.5 35.5 68.7 48/1.35 40.0 45.5 2800 20.0 810 540
500 26.5 5.5 39.2 68.7 48/1.35 43.5 49.5 3250 25.0 880 590
630 30.0 5.5 43.0 68.7 48/1.35 47.5 53.5 3800 32.0 960 640
800 36.0 5.5 47.5 68.7 48/1.35 52.0 58.0 4450 40.0 1040 690
1000 40.2 5.5 54.5 68.7 48/1.35 59.0 65.5 5400 50.0 1170 780