PRODUCTS

AS/NZS Single Core 19/33KV XLPE Insulated
Description

Application:
       This cable is used for urban networks. It can be installed aerially, in conduit, on open trays and in underground ducts 
Operating temperature:
       90 & & &,,,,,
 
Voltage rating:
       19/33KV
Construction:
      Conductor: Compact round stranded copper or aluminium
      Conductor Shield: Semi-conducting tape and /or semi-conducting cross-linked polyethylene
      Insulation: Cross-linked polyethylene
      Insulation Shield: Semi-conducting cross-linked polyethylene
      Shield: Copper wire shield
       Filler: Polypropylene (Nonhygroscopic material)
       Binding Tape: Polyester and/or non-woven tape (Optional: water blocking tape)
      Sheath: Black polyvinylene (Optional: polyvinyl chloride)

Insulation colour:
     Natural

Followed standard:
      AS/NZS1429.1,AS/NZS1125
Construction data: 
      
Copper conductor,10KA Fault Level   

 
Nominal Cross sectional area Reference conductor diameter Nominal insulation thickness Nominal diameter over insulation Nominal screen area on each core Number and nominal diameter of screen wires Nominal over screen wire Approx overall diameter Approx weight of cable Max.
puling tension
Min.bending radius
During pulling Set in position
mm2 mm mm mm mm2 mm mm mm kg/km KN mm mm
50 8.4 8.0 25.5 48.7 34/1.35 30.0 34.5 1700 3.5 620 410
70 10.0 8.0 27.5 68.7 48/1.35 31.5 36.5 2150 4.9 650 430
95 11.7 8.0 29.0 68.7 48/1.35 33.5 38.5 2450 6.7 680 460
120 13.2 8.0 31.0 68.7 48/1.35 35.0 40.0 2800 8.4 720 480
150 14.5 8.0 32.0 68.7 48/1.35 36.5 41.5 3100 11.0 750 500
185 16.2 8.0 34.0 68.7 48/1.35 38.5 43.5 3450 13.0 780 520
240 18.4 8.0 36.0 68.7 48/1.35 40.5 46.0 4100 17.0 830 550
300 20.6 8.0 38.5 68.7 48/1.35 43.0 48.5 4750 21.0 870 580
400 23.8 8.0 41.5 68.7 48/1.35 46.0 51.5 5750 28.0 930 620
500 26.5 8.0 44.5 68.7 48/1.35 49.0 55.0 6850 35.0 990 660
630 30.0 8.0 48.0 68.7 48/1.35 52.5 59.0 8150 44.0 1060 710
800 36.0 8.0 54.0 68.7 48/1.35 58.5 65.5 10200 56.0 1180 780
1000 40.2 8.0 59.5 68.7 48/1.35 64.0 71.5 12200 70.0 1280 850



 



 




















       Aluminum conductor,10KA Fault Level 
Nominal Cross sectional area Reference conductor diameter Nominal insulation thickness Nominal diameter over insulation Nominal screen area on each core Number and nominal diameter of screen wires Nominal over screen wire Approx overall diameter Approx weight of cable Max.
puling tension
Min.bending radius
During pulling Set in position
mm2 mm mm mm mm2 mm mm mm kg/km KN mm mm
50 8.4 8.0 26.0 32.9 23/1.35 30.0 34.5 1250 2.5 620 410
70 10.0 8.0 27.5 45.8 32/1.35 31.5 36.5 1500 3.5 650 430
95 11.7 8.0 29.0 61.5 43/1.35 33.5 38.0 1800 4.8 680 450
120 13.2 8.0 30.5 68.7 48/1.35 35.0 39.0 2005 6.0 710 470
150 14.5 8.0 32.0 68.7 48/1.35 36.5 41.5 2150 7.5 740 490
185 16.2 8.0 33.5 68.7 48/1.35 38.0 43.0 2300 9.3 770 510
240 18.4 8.0 35.5 68.7 48/1.35 40.0 45.5 2550 12.0 810 540
300 20.6 8.0 38.0 68.7 48/1.35 42.5 48.0 2850 15.0 860 570
400 23.8 8.0 41.0 68.7 48/1.35 45.5 51.5 3200 20.0 920 610
500 26.5 8.0 44.5 68.7 48/1.35 49.0 55.0 3700 25.0 980 660
630 30.0 8.0 48.0 68.7 48/1.35 52.5 59.0 4300 32.0 1050 700
800 36.0 8.0 52.5 68.7 48/1.35 57.0 63.5 5000 40.0 1140 760
1000 40.2 8.0 59.5 68.7 48/1.35 64.0 71.5 6000 50.0 1270 850