AS/NZS Three Core 19/33KV XLPE Insulated
Description

Application:
       This cable is used for urban networks. It can be installed aerially, in conduit, on open trays and in underground ducts 
Operating temperature:
       90 & & &,,,,,
 
Voltage rating:
       19/33KV
Construction:
       Conductor: Compact round stranded copper or aluminium
       Conductor Shield: Semi-conducting tape and /or semi-conducting cross-linked polyethylene
       Insulation: Cross-linked polyethylene
       Insulation Shield: Semi-conducting cross-linked polyethylene
      Shield: Copper wire shield
       Filler: Polypropylene (Nonhygroscopic material)
       Binding Tape: Polyester and/or non-woven tape (Optional: water blocking tape)
       Armour:Galvanized steel wire
      Sheath: Black polyvinylene (Optional: polyvinyl chloride)

Insulation colour:
     The individual cores shall be identified by the colored strip tapes ,applied under the metallic shielding layer

Followed standard:
      AS/NZS1429.1,AS/NZS1125
Construction data: 
      
Copper conductor,10KA Fault Level  

Nominal Cross sectional area

Reference conductor diameter Nominal insulation thickness Nominal diameter over insulation Nominal screen area on each core Number and nominal diameter of screen  wires Nominal over screen wire Unarmoured Steel wire armoured
Approx overall diameter Approx weight of cable Nominal diameter over armour Approx overall diameter Approx weight of cable
mm2 mm mm mm mm2 mm mm mm kg/km mm mm kg/km
50 8.4 8.0 25.5 49.4 29/0.85 29.0 70.5 4600 74.0 81.5 9500
70 10 8.0 27.5 68.1 40/0.85 31.0 74.0 5600 77.5 85.0 10800
95 11.7 8.0 29.5 68.1 40/0.85 33.0 79.0 6650 81.5 90.0 12200
120 13.2 8.0 31.0 68.1 40/0.85 34.5 82.5 7650 85.5 93.5 13400
150 14.5 8.0 32.5 68.1 40/0.85 36.5 86.0 8750 89.5 97.5 14900
185 16.2 8.0 34.0 68.1 40/0.85 37.5 89.5 9900 92.5 101.5 16300
240 18.4 8.0 36.5 68.1 40/0.85 40.5 96.0 11900 98.0 107.0 18800
300 20.6 8.0 38.5 68.1 40/0.85 13.0 101.0 14100 103.5 113.0 21400
400 23.8 8.0 41.5 68.1 40/0.85 45.5 108.0 17300 110.0 120.0 25100
500 26.8 8.0 44.5 68.1 40/0.85 48.5 114.5 20700 117.0 127.0 29000

      Aluminum conductor,10KA Fault Level 
Nominal Cross sectional area Reference conductor diameter Nominal insulation thickness Nominal diameter over insulation Nominal screen area on each core Number and nominal diameter of screen  wires Nominal over screen wire Unarmoured Steel wire armoured
Approx overall diameter Approx weight of cable Nominal diameter over armour Approx overall diameter Approx weight of cable
mm2 mm mm mm mm2 mm mm mm kg/km mm mm kg/km
50 8.4 8.0 25.8 32.3 19/0.85 29.5 71.0 3550 74.0 82.0 8500
70 10 8.0 27.5 46.0 27/0.85 31.0 75.0 4150 78.0 85.5 9350
95 11.7 8.0 29.0 61.3 36/0.85 33.0 78.5 4800 81.5 89.5 10300
120 13.2 8.0 30.5 68.1 40/0.85 34.5 82.0 5250 84.5 93.0 11000
150 14.5 8.0 32.0 68.1 40/0.85 36.0 85.0 5800 89.0 97.0 11900
185 16.2 8.0 33.5 68.1 40/0.85 37.5 89.0 6350 91.5 100.5 12700
240 18.4 8.0 35.8 68.1 40/0.85 40.0 94.5 7300 97.0 106.0 14000
300 20.6 8.0 38.0 68.1 40/0.85 42.5 100.0 8200 102.0 112.0 15400
400 23.8 8.0 41.0 68.1 40/0.85 46.0 106.5 9550 109.0 118.5 17200
500 26.8 8.0 44.5 68.1 40/0.85 49.0 114.5 11200 117.0 127.5 19600